| · Floor space divided into Facility Management Suites of various sizes and consists of physically separated areas for shared and dedicated facilities with their own access controls · Shared Meeting Room Facility for client use · Disaster Recover (DR) facilities for dedicated / shared use that including telephones, desks, shared printer & fax facilities |
| · Single-story steel and concrete construction · Built in 2008 / 09 · Ceilings, walls, floors and doors comply at least with RF90 (fire resistance 90 minutes) in data centre areas, telecom rooms, and plant areas · Poured Concrete Solid Slab Floor |
Floor Specification and Dimensions | · Data center rooms have a raised access · Floor to ceiling clearance of 13 feet |
| · Physically guarded 24/7 · CCTV perimeter, common area and Facility Management Suite coverage · Iris access system with movement logs · Mantraps with weight sensors at every entry point · Internal and external intruder detection devices; - Motion Sensors - Heat Sensors - Glass Break Sensors - Seismic Sensors - Roof Penetration Sensors · Vehicle entrance barriers (front and rear of building) · Water sensors on all floor areas within Data Centre, Facility Management Suites and mechanical rooms |
Fire Detection / Suppression | · Fitted with a 2 stage fire detection system · Systems monitoring under floor, room and ceiling void spaces · Fire Department automatic dispatch upon alarm detection · Fire Department station located within 4km (2.5miles) · Data center area fitted with dry action sprinkler system |
Cooling Facilities | · In-room air conditioning provided at N+1 redundant unit · Glycol /condensed water cooling system · In-suite systems provide full function control air conditioning system, with cooling, humidity and de-humidification control · Room design temperature: 22 degrees C, plus or minus 1 degree C · Room humidity: 50% rH. Plus 10% or minus 10% rH · External Temperature Design: 35 degree C Dry Bulb |
Electrical Power Supply | · Capacity up to 6MW 3 phase electrical supply · Standby Generation is provided at N+1 redundancy via diesel engine driven generators · Onsite fuel stores for 72 hours of continuous running · Backup deliveries are available from diverse supply depots · UPS is available to provide N+1 redundancy for critical computer supplies · Each UPS can support the facilities for 15 minutes at full load · Automatic transfer switches for automatic generation startup/synchronization · Harmonic Mitigating Transformers for all DC feeds (HMT) · AC & DC currents available to any suite |
Connectivity | · Diverse Fiber Entrances to the facility · Fully Managed IP Services · Peering to over 100 carrier networks & content providers (including; Google, Q9, TATA, Cogent, Verizon, Allstream, XO, Level3) · Cisco Network Infrastructure with Advanced BG |